Fire Testing Equipment

Limiting Oxygen Index Tester

This is some text inside of a div block.

The Oxygen Index is a quality control test of combustible materials. Its ease of use together with high levels of precision has made this technique a primary characterizing and quality control. The technique measures the minimum percentage of oxygen in the test atmosphere that is required to marginally support combustion. The oxygen tester is used to check combustion of plastic materials such as polymers, cables, rubber, nylon, laminates, fabrics etc. The advanced LOI Limiting Oxygen Index Tester accurately determines the relative flammability of plastics and other materials. It conforms to ASTM D2863 and ISO 4589-1, ISO 4589-2 standards and provides a means for safely determining the relative flammability of materials by measuring the minimum oxygen concentration that will support combustion. The test specimens are burned in a precisely controlled atmosphere of nitrogen and oxygen. The operator adjusts the supply gases and uses the flowmeter readings to calculate the oxygen index.

ISO 4589-2 and ASTM D2863, gives the procedure for determination of Limited oxygen index of materials.

ISO 4589 specifies methods for determining the minimum concentration of oxygen, in added mixture with nitrogen, that will support combustion of small vertical test specified test conditions The results are defined as oxygen index values.

Features & Technical Specifications

Features :

  • Digital display of Paramagnetic oxygen analyzer with accuracy 0.1%
  • Easy to Operate – User needs only to ignite specimen and adjust gas flow
  • Flexible Sample Testing – Specimens may be in rod, film or composite form
  • Uniform Combustion Atmosphere – Nitrogen and oxygen are fully mixed in a special dispersion chamber and glass bead bed before entering column
  • Precision Gas Flow Metering – Micro-adjustment flowmeters allow precise control of gases
  • Conforms to ASTM D2863 and ISO 4589-1, ISO 4589-2
  • Twin Gas Flowmeters with Control Needle Valves, Certified Calibration to ±0.5%
  • Twin Gas Pressure Gages (0 to 100psi)
  • Chimney Gas Dispersion Chamber with Glass Bead Bed
  • Rigid Specimen Holder

Standard Features :

  • Twin Gas Flowmeters with Control Needle Valves, Certified Calibration to ±0.5%
  • Twin Gas Pressure Gages (0 to 100psi)
  • Chimney Gas Dispersion Chamber with Glass Bead Bed
  • Rigid Specimen Holder

Specifications :

  • Dimensions : 20”H × 12”W × 12.4”D (50.8cm × 30.5cm × 31.5cm)
  • Weight : 32.5 Ibs. (14.7kg)
  • Gas Requirement : Commercial grade or better Nitrogen (N₂) and  Oxygen (O₂)